Objective:
To study the performance of various
types of controllers used to control the temperature of an oven.
Apparatus Required:
Graph sheet
System Description:
Temperature control is one
of the most common industrial control systems that are in operation. This
equipment is designed to expose the students to the intricacies of such a
system in the friendly environment of a laboratory, free from disturbances and
uncertainties of plant prevalent in an actual process. The ‘Plant’ to be controlled
is a specially designed oven having a short heating and cooling time. The
temperature time data may be obtained manually, thus avoiding expensive
equipment like an X-Y recorder or a pen recorder. A solid state temperature
sensor converts the absolute temperature information to a proportional
electrical signal. The reference and actual temperatures are indicated in
degree Celsius on a switch selectable digital display.
The controller unit
compares the reference and the measured signals to generate the error.
Controller options available to the user consists of ON-OFF or relay with two
hysteresis settings and combination of proportional, derivative and integral
blocks having independent coefficient settings. A block diagram of the complete
system is shown below:
Block Diagram |
The
Plant (Oven):
Plant to be controlled is
an electric oven, the temperature of which must adjust itself in accordance
with the reference or command. This is a thermal system which basically
involves transfer of heat from one section to another. In the present case we
are interested in the transfer of heat from the heater coil to the oven and the
leakage of heat from the oven to the atmosphere.
Controllers:
Basic control actions
commonly used in temperature control systems are
- ON-OFF or relay
- Proportional
- Proportional and integral
- Proportional-Integral-Derivative
All the four controllers
have been used here. The parameter constants are listed below:
Proportional
Gain (KP) = 0 to 0.1V/0C
Integral
Gain (KI) = 0 to 0.024/sec
Derivative
Gain (KD) = 0 to 23.5 sec
Sensor:
The
oven temperature can be sensed by a variety of transducers like thermistor,
thermocouple, RTD and semiconductor sensors. In the present set up, the maximum
oven temperature is around 900C which is well within the operating
range of a semiconductor temperature sensor like AD590. Further these sensors
are linear and have a good sensitivity, viz. 1µA/0K. Associated
electronic circuits convert this output to 10mV/0C which may be
easily measured by a DVM. The time constant of the sensor has however been
neglected in the analysis since it is insignificant compared with the oven time
constant.
Experimental
work:
A
variety of experiments may be conducted with the help of this unit. The
principal advantage of the unit is that all power sources and metering are
built in and one needs only a Watch
to be able to note down the temperature readings at precise time constants.
After each run the oven has to be cooled to nearly the room temperature, which
may take about 15-20 minutes.
1. Identification
of oven parameters:
In
the open loop testing, the oven is driven through the P-amplifier set to its
maximum gain of 10. The input to this amplifier is adjusted through reference
potentiometer (the one next to switch 2). This input can be seen on digital
display, so that when you set 50C, the input to proportional
amplifier is 50mV (@ 10mV/0C) and its output (which acts as input to
driver/actuator) is 0.5V.
Procedure:
- Keep switch S1 to ‘WAIT’, S2 to ‘SET’ and open ‘FEEDBACK’ terminals.
- Connect P output to the actuator input and switch ON the unit.
- Set P potentiometer to 1. Adjust reference potentiometer to read 5.0 on the DPM. This provides an input of 0.5V to the driver.
- Put switch S2 to the ‘MEASURE’ position and note down the room temperature.
- Put S1 to the ‘RUN’ position and note temperature readings every 15 sec., till the temperature becomes almost constant.
- Plot temperature-time curve on a graph paper. Referring to the fig shown below, calculate T1 and T2 and hence write the transfer function of the oven as:
\[G(s) = \frac{{K{e^{ - S{T_2}}}}}{{(1 + S{T_1})}}\]
Open Loop Response |
2. ON-OFF Controller:
- Switch S1 to ‘WAIT’ position and allow the oven to cool to room temperature. Short ‘FEEDBACK’ terminals.
- Keep switch S2 to the ‘SET’ position and adjust reference potentiometer to the desired output temperature, say 55.00C, by seeing on DPM.
- Connect R output to the actuator/driver input. Outputs of P, I and D must be disconnected from the actuator input. Select ‘HI’ or ‘LO’ value of hysteresis.
- Switch S2 to ‘MEASURE’ and S1 to ‘RUN’ position. Read and record oven temperature every 15-30 sec., for about 20 minutes.
- Plot a graph between temperature and time and observe the oscillations in the steady state. Note down the magnitude of oscillations, rise time, percent overshoot and steady state error.
3. Proportional Controller:
Ziegler
and Nichols suggest the value of KP for P controller as
KP=
(1/K) X (T1/T2)
K = Oven Temperature at steady / Input voltage (V).
%
of P controller value = KP/0.1 X 100%
- Starting with a cool oven, switch S1 to ‘WAIT’ position and connect P output to the actuator input. Keep R, D and I outputs disconnected. Short ‘FEEDBACK’ terminals.
- Set P potentiometer to the above calculated value.
- Select and set the desired temperature to say 55.00C.
- Switch S1 to ‘RUN’ position and record temperature readings as before.
- Plot the temperature-time data on a linear graph paper and observe the rise time, steady state error and percent overshoot.
4. Proportional-Integral Controller:
Ziegler
and Nichols suggest the value of KP and KI for P-I
controller as
KP
= (0.9/K)X (T1/T2), KI =1/T1=1/3.3T2.
Keep
T2 constant and T1=3.3T2
%
of I controller value = KI/0.0244 X 100%.
- Starting with a cool oven, switch S1 to ‘WAIT’ position and connect P and I output to the actuator input. Keep R and D outputs disconnected. Short ‘FEEDBACK’ terminals.
- Set P and I potentiometers to the above calculated values.
- Select and set the desired temperature to say 55.00C.
- Switch S1 to ‘RUN’ position and record temperature readings as before.
- Plot the temperature-time data on a linear graph paper and observe the rise time, steady state error and percent overshoot.
5. Proportional-Integral-Derivative
Controller:
Ziegler
and Nichols suggest the value of KP, KD and KI
for P-I controller as
KP
= (1.2/K)X (T1/T2), KI =1/T1=1/2T2,
KD = 0.5T2.
Keep
T2 constant and T1=2.0T2
%
of D controller value = KD/23.5 X 100%.
- Starting with a cool oven, switch S1 to ‘WAIT’ position and connect P, D and I output to the actuator input. Keep R outputs disconnected. Short ‘FEEDBACK’ terminals.
- Set P, D and I potentiometers to the above calculated values.
- Select and set the desired temperature to say 55.00C.
- Switch S1 to ‘RUN’ position and record temperature readings as before.
- Plot the temperature-time data on a linear graph paper and observe the rise time, steady state error and percent overshoot.
- Compare the results of various controller options.
very helpful for lab assignment
ReplyDeletevery helpful
ReplyDeleteI have just gone through your blog......your information is so valuable. Thanks for sharing this information. HEATTEC SYSTEMS (PRIVATE) LIMITED made a commitment towards the research and development of new and improved products, abortion thus keeping in mind diversified customers to provide the customers with superior products and services for their individual needs.Temperature Controller in Sri Lanka
ReplyDeleteAi Furnaces is the premium manufacturer of High-Quality Forced Air Drying Ovens and Lab Vacuum Ovens.
ReplyDeleteInteresting article! Thank you for sharing them! I hope you will continue to have similar posts to share with everyone.
ReplyDeleteSafety Valve China
Ai Furnaces is the Leading Manufacturer of Lab Furnaces and Ovens, where you can choose from analog, basic digital and programmable laboratory ovens and furnaces.
ReplyDeleteWhat are the lab ovens, what are the sizes of lab ovens, the temperature range of lab ovens and what you should consider when buying a lab oven?
ReplyDelete